47 changes: 47 additions & 0 deletions docs/section23/Rule23-17.md
Original file line number Diff line number Diff line change
@@ -0,0 +1,47 @@

# Airside System - Rule 23-17

**Schema Version:** 0.0.34
**Mandatory Rule:** TRUE
**Rule ID:** 23-1
**Rule Description:** System 2 and 4 - Electric air-source heat pumps shall shall be modeled to continue to operate while auxiliary heat is energized.
**Rule Assertion:** B-RMR = expected value
**Appendix G Section:** Section 23 Air-side
**90.1 Section Reference:** G3.1.3.1 Heat Pumps (Systems 2 and 4)
**Data Lookup:** None
**Evaluation Context:** HVAC System

**Applicability Checks:**

1. B-RMR is modeled with at least one air-side system that is Type-2, or 4

**Function Calls:**

1. get_baseline_system_types()
2. baseline_system_type_compare()
3. get_component_by_id()

**Applicability Checks:**
- create a list of the target system types: `APPLICABLE_SYS_TYPES = [HVAC_SYS.SYS_2,HVAC_SYS.SYS_4]`
- Get B-RMR system types: `baseline_system_types_dict = get_baseline_system_types(B-RMR)`

- loop through the applicable system types: `for target_sys_type in APPLICABLE_SYS_TYPES:`
- and loop through the baseline_system_types_dict to check the system types of the baseline systems: `for system_type in baseline_system_types_dict:`
- do baseline_system_type_compare to determine whether the baseline_system_type is the applicable_system_type: `if((baseline_system_type_compare(system_type, target_sys_type, false)):`
- the systems in the list: baseline_system_types_dict[system_type] are sys-2 or 4 - loop through the list of systems: `for hvac_system_id in baseline_system_types_dict[system_type]:`
- `CONTINUE TO RULE LOGIC`
- otherwise, rule not applicable: `else: RULE_NOT_APPLICABLE`

**Rule Logic:**
- get the hvac system from the hvac_system_id: `hvac_system = get_component_by_id(hvac_system_id)`
- get the heating system: `heating_system = hvac_system.heating_system`
- get the heatpump_low_shutoff_temperature = `heatpump_low_shutoff = heating_system.heatpump_low_shutoff_temperature`

**Rule Assertion:**
- Case 1: The heat pump low shutoff temperature equal to the flag of -999, which indicates that there is no low-temperature shutoff for the heatpump: `if heatpump_low_shutoff <= -999: PASS`
- Case 2: all other cases: FAIL: `else: FAIL`

**Notes:**
1. The minimum temperature is not finalized and is up for discussion. Must coordinate with the note provided in the schema element: HeatingSystem.heatpump_low_shutoff_temperature

**[Back](../_toc.md)**