You signed in with another tab or window. Reload to refresh your session.You signed out in another tab or window. Reload to refresh your session.You switched accounts on another tab or window. Reload to refresh your session.Dismiss alert
Button touched, 5-bits for the 5 different touch zones (1:Top-Left, 2:Top-Right, 4:Center, 8:Bottom-Left, 16:Bottom-Right), multiple buttons are possible.
Digital
0x00
Backlight/Buzzer
S→E
Bit 0:Backlight output on/off, Bit 1:Buzzer on/off
Analog
0x00
Temperature
S←E
Temperature in Celcius, sent every n minutes and after startup. Signed value multiplied by 1000.0 (scaling factor 5).
Analog
0x01
Humidity
S←E
Humidity in Percent, sent every n minutes and after startup. Signed value multiplied by 1000.0 (scaling factor 5).
Configuration Version 2:
Offset
Value
Description
8…11
1
Send interval for temperature and humidity in minutes